Relevant section: External power supply & fail-safe electric lock with REx and motion sensor with dry contact
YOU WILL NEED
- Kisi Controller Pro 1 (comes with a 24V Universal AC power supply)
Not included with Kisi purchase:
- 12 or 24V DC fail safe electric strike or magnetic lock
- Ethernet Cable
- Low Voltage Wires
- External Power Supply for lock
- Push to exit button/motion sensor
- Keypad
Part | Connection |
Maglock |
Negative (-) lead from the Maglock to the Normally Closed (NC) connection on the Push to Exit button. Positive (+) lead from the Maglock to the Normally Closed (NC) output of the Power Supply's output. |
Push to Exit |
Common (COM) on your Push to Exit to the Common (COM) of the Motion Sensor. Normally Closed NC connection on the Push to Exit button to the negative (-) lead from the Maglock. |
Motion Sensor |
Normally Closed (NC) of the Motion Sensor to the Common (COM) of the Power Supply's output. Common (COM) of the Motion Sensor to the Common (COM) on your Push to Exit. |
Power Supply |
Common (COM) of the Power Supply's output to Normally Closed (NC) of the Motion Sensor. Normally Closed (NC) output of the Power Supply's output to the Positive (+) lead from the Maglock. |
Kisi Controller |
Connect the low voltage wiring from Common (COM) on the Kisi controller to Ground (GND) on the Power Supply's input. Normally Open (NO) on the Kisi controller to In (IN) on the Power Supply's input. |
Here is the text version:
1. First, you will want to connect the negative (-) lead from the Maglock to the Normally Closed NC connection on the Push to Exit button.
2. Next, you will connect the Common (COM) connection on your Push to Exit to the Common (COM) connection of the Motion Sensor.
3.Next, you will connect the Normally Closed (NC) connection of the Motion Sensor to the Common (COM) connection of the Power Supply's output.
4. Next, you will connect the positive (+) lead from the Maglock to the Normally Closed (NC) output connection of the Power Supply's output.
5. Lastly, you will connect the low voltage wiring from Common (COM) on the Kisi controller to Ground (GND) on the Power Supply's input, and Normally Open (NO) on the Kisi controller to In (IN) on the Power Supply's input.